40A is too high for 6mm, should be 32A. Also the length of the cable run has a big impact on whether 6mm is a big enough cable…..! Its generally ok but can struggle for long runs.

Can 6mm cable Take 40A?

40A is too high for 6mm, should be 32A. Also the length of the cable run has a big impact on whether 6mm is a big enough cable…..! Its generally ok but can struggle for long runs.

Does an electric shower need an RCD?

Electric Showers All circuits in a bathroom must be protected by a RCD (Residual Current Device). They will need to be connected to the consumer unit and protected by an RCD.

Does an electric shower have a fuse?

For example, an electric shower with 8.5kW fuse is alright with 40 amperes. It is also advisable not to get a fuse that is significantly higher than what is required….The Right Fuse for Your Electrical Shower.

Kilowatt Rating Fuse Size
7.5 kW 40 amperes
8.5 kW 40 amperes
9.0 kW 40 amperes
9.5 kW 40 amperes

What size cable do I need for 40 amps?

For a maximum of 40 amps, you’ll need a wire gauge of 8. Many electric cooking appliances require 40 amps such as electric cooktops.

Can you put a 6mm cable on a 40 amp MCB?

6mm twin and earth cable (which this almost certainly is) can be backed up by a maximum of a 32a MCB, even lower if other factors are involved. You’ll need that 10mm cable and a 40a MCB unfortunately as your shower is going to draw over 32a. Whoever fitted the 40a MCB onto the 6mm cable originally was in the wrong.

How many amps does an electric shower use?

Electric Shower Power Ratings and Power Cable Information Fuses and switches should be rated at 32 amps. Showers up to 9kw may carry a 6mm cable as long as the shower unit is within 18 meters of the fuseboard. Fuses and switches should be rated at 40 amps.

What breaker do I need for a shower?

Normally for a shower it woul be a 40 or 45amp fuse/circuit breaker. 9000watts divided by 230volts = just over 39 amps. Its also worth checking that you have an RCD (redisual current device) fitted, as all showers must now be RCD protected.

What type MCB for a shower?

Any shower over 8kw requires a 10mm cable. 50 amp mcb, but crucially backed up by an RCD/RCBO.

What size MCB for a shower?

The shower is currently protected by a 32A mcb which is protected along with other circuits by an rcd for the consumer unit. The cable size is 6mm.

What amperage is an electric shower?

40 amps
Electric Shower Power Ratings and Power Cable Information Fuses and switches should be rated at 40 amps. Showers up to 12.5kw should carry a 10mm cable to units within 35 metres of the fuseboard. Fuses and switches should be rated at 50 amps.

What size MCB for 10.8 kW shower?

45 amp
A ‘maintained pressure’ (also known as ‘running pressure’) exists when other draw offs are being used. When replacing a 9.5kW electric shower with a 10.8kW, the MCB tips out each time it’s used. Why is this? First, check the MCB current rating; a shower of this kilowatt rating should have a 45 amp.

https://www.youtube.com/watch?v=f2i6eH27rV8